ORBIT MK M Z 1ExdbIICT6Gb/ExtbIIICT85°CDb

ORBIT MK M Z 1ExdbIICT6Gb/ExtbIIICT85°CDb
Price on request
Housing material:
  • A - aluminum alloy
  • N - stainless steel
You choosed:

    Explosion-proof fire alarms
    Orbita MK M-Z series

    The Orbita MK M-Z alarm devices are designed to generate alarm signals in fire and security alarm systems, to attract the attention of personnel in industrial emergencies. The alarm devices can be used with any fire and security alarm control and monitoring devices. The type and level of explosion protection are 1 Ex db IIC T 6 Gb / Ex tb IIIC T 85 ° C Db, PB Ex db I Mb / 1 Ex db IIC T6 Gb / Ex tb IIIC T85 ° C Db according to GOST R IEC 60079-0-2011. The alarm devices can be used in hazardous areas and rooms of classes 1 and 2 according to GOST IEC 60079-10-1-2011 and GOST IEC 60079-14-2011.

    The alarms have two warning stages and different operating modes, each independent of the other. Switching between warning stages is accomplished in one of two ways:

    • external control signal;
    • automatically - by timer.

     

    The notification mode is set using a group of microswitches.

    The alarms are produced with the following supply voltage:

    • 12-27V DC;
    • 220V AC.

     

    Distinctive features:

    • fully sealed housing with IP67 protection rating;
    • two-stage notification with automatic or external control;
    • a wide range of different types of sound notifications, independently for each stage;
    • independent programming of the operating mode by the user;
    • high power sound alert;
    • A wide selection of certified cable entries for any connection option.

     

    The posts are equipped with explosion-proof cable entries of the KV series, KV TU 27.33.13-138-81888935-2019. The connecting thread of the cable entries is M20x1.5. Cable entries allow the input and output of round cables of various diameters.

    Table 1

    Explosion protection marking

    1 Ex db IIC T6 Gb/Ex tb IIIC T85 °C Db,
    PB Ex db I Mb/ 1 Ex db IIC T6 Gb/Ex tb IIIC T85 °C Db

    Degree of protection of the shell

    IP67

    Climatic performance

    UHL1

    Operating temperature range

    -60C<Ta<+70C

    Supply voltage:

    Orbit MK M-Z

    Orbit MK M-Z 220

     

    10.8V - 27V DC

    ~220V +10% -15% AC 50Hz

    Current consumption, no more than:

    Orbit MK M Z

    Orbit MK M Z220

     

    0.4Adc

    0.1Aac

    Sound pressure level

    117±5 dB

    Number of alarm stages

    2

    Number of sound signals for each stage (see table 2)

    7

    Number of sound signal combinations

    42

    Time delay for automatic switching to the second stage

    2 min.

    Body material

    Aluminum alloy

    Stainless steel

    Overall dimensions (L x W x H), mm, no more than

    150 x 150 x 102.5

    Weight, no more than:

    1.1 kg.

     

    Operating modes

    Table 2

    Signal Signal Description Signal type
    0 no sound  
    1 2.3 kHz siren, frequency modulation ±10% with a period of 1 Hz
    2 2.3 kHz siren, frequency modulation ±10% with a period of 2 Hz
    3 2.3 kHz trill, frequency modulation ±10% with a period of 7 Hz
    4 intermittent 2.3 kHz, repetition period 1 Hz
    5 intermittent 2.3 kHz, repetition period 2 Hz
    6 frequency switching 2..2.3 kHz, period 2 Hz
    7 continuous with a frequency of 2.3 kHz

     

    The operating mode is selected by the user using dip switches. Single-stage or two-stage operation is possible. The second stage is activated automatically after a fixed time or by an external control signal. The type of audible alert signal is selected independently for each stage using dip switches (Table 2).

     

    Ordering designation system:

    ORBIT MK M Z 220 - A - TO
    1 2 3 4 5

     

    1. Series of detectors;
    2. Alert type:
      - Z – sound;
    3. Supply voltage:
      - no designation – 12-27V;
      - 220 - alternating voltage 220V;
    4. Body material:
      - A - aluminum alloy;
      - H - corrosion-resistant steel 12X18H10T;
    5. Fitting type:
      - B - for armored cable;
      - T3/4 - for laying cable in a pipe with a G3/4-B connecting thread;
      - T1/2 - for laying cable in a pipe with a G1/2-B connecting thread;
      - K - for open cable installation;
      - KM15 – for cable or armored cable in a metal sleeve RZ-TsKh-15mm;
      - KM20 – for cable or armored cable in a metal sleeve RZ-TsKh-20mm.